| Specifications
| Product Glance | Value |
| Model | ANTRACK |
| Version | AR31 |
| Capacity | 20 units ANTMINER (U2 Hydro) or 14 units ANTMINER (T-type Hydro) |
| Miner maximum load,kW | 200 |
| Total load, kW | 215 |
| Detailed Characteristics | Value |
| Part 1: Mining Cabinet | |
| Hardware Configuration | |
|
Size (Length*Width*Height), mm (without package) |
1,000*1,200*2,300 |
|
Size (Length*Width*Height), mm (with package) |
1,070*1,380*2,400 |
|
Net weight, kg (without package) |
640 |
|
Gross weight, kg (with package) |
750 |
|
Network connection mode |
RJ45 Ethernet 10/100M |
| Power Supply | |
| Power supply AC Input voltage, Volt(1-1) | 380~480V AC |
| Power supply AC Input Frequency Range, Hz | 50~60 |
| Power supply AC Input current, Amp(1-2) | 326 @ 380V 270 @ 480V |
| Water pump | |
|
Rated power, kW |
7.5 |
|
Noise, dBA@1m |
79 |
| Lift, m | 73 |
| Size (Length*Width* Height), mm | 618*248*300 |
| Part 2: External Cooler(1-3) | |
| Hardware Configuration | |
| Size (Length*Width*Height), mm (without package) | 1,200*2,250*2,300 |
| Size (Length*Width*Height), mm (with package) | 1,250*2,320*2,400 |
| Net weight, kg (without package) |
550 |
| Gross weight, kg (with package) |
700 |
| Power supply | |
| Power supply AC input voltage, Volt(1-1) | 380~480V AC |
| Power supply AC input frequency range, Hz | 50~60 |
| Maximum power supply AC input current, Amp(1-2) | 15.8 @ 380V 14.8 @ 480V |
| Fan | |
| Rated power, kW |
4.1 * 2 @ 380V |
| Noise, dBA@1m |
78 |
| Size (Length*Height*Thickness), mm |
1,070*1,070*330 |
| Plate heat exchanger (optional) | |
| Maximum heat exchange power, kW |
200 |
| Size (Length*Width* Height), mm |
490*235*250 |
| Diameter of water pipe connector, mm | DN50 |
| Environment Requirements | |
| Ambient temperature, °C | -20~44 |
| Water flow, L/min | 320~350 |
| Water pressure, bar | ≤3.5 |
| Working fluid(1-4) | Organic Antifreeze (10%) |
| Installation distance, m(1-5) | 5 |
| Liquid PH | 7.8~8.5 |
| Storage temperature, °C | -40~70 |
| Operation humidity(non-condensing), RH | 10~90% |
Notes:
(1-1) Caution: Wrong input voltage may cause server damaged.
(1-2) Three-phase AC input.
(1-3) The External cooler should be placed outdoors in a well-ventilated environment.
(1-4) If the water conductivity is ≥100 μs/cm, the fluid must be replaced. The water conductivity is less than 20 μs/cm when the system is running at the first time.
(1-5) The maximum distance between mining cabinet and external cooler.









Reviews