| Specifications


 

Product Glance Value
Model ANTRACK
Version AR31
Capacity 20 units ANTMINER (U2 Hydro) or 14 units ANTMINER (T-type Hydro)
Miner maximum load,kW 200
Total load, kW 215

 

Detailed Characteristics Value
Part 1: Mining Cabinet  
Hardware Configuration  

Size (Length*Width*Height), mm (without package)

1,000*1,200*2,300

Size (Length*Width*Height), mm (with package)

1,070*1,380*2,400

Net weight, kg (without package)

640

Gross weight, kg (with package)

750

Network connection mode

RJ45 Ethernet 10/100M
Power Supply  
Power supply AC Input voltage, Volt(1-1) 380~480V AC
Power supply AC Input Frequency Range, Hz 50~60
Power supply AC Input current, Amp(1-2) 326 @ 380V
270 @ 480V
Water pump  

Rated power, kW

7.5

Noise, dBA@1m

79
Lift, m 73
Size (Length*Width* Height), mm 618*248*300
Part 2: External Cooler(1-3)  
Hardware Configuration  
Size (Length*Width*Height), mm (without package) 1,200*2,250*2,300
Size (Length*Width*Height), mm (with package) 1,250*2,320*2,400
Net weight, kg (without package)

550

Gross weight, kg (with package)

700

Power supply  
Power supply AC input voltage, Volt(1-1) 380~480V AC
Power supply AC input frequency range, Hz 50~60
Maximum power supply AC input current, Amp(1-2) 15.8 @ 380V
14.8 @ 480V
Fan  
Rated power, kW

4.1 * 2 @ 380V
4.7 * 2 @ 480V

Noise, dBA@1m

78

Size (Length*Height*Thickness), mm

1,070*1,070*330

Plate heat exchanger (optional)  
 Maximum heat exchange power, kW

200

Size (Length*Width* Height), mm

490*235*250

Diameter of water pipe connector, mm DN50
Environment Requirements  
Ambient temperature, °C -20~44
Water flow, L/min 320~350
Water pressure, bar ≤3.5
Working fluid(1-4) Organic Antifreeze (10%)
Installation distance, m(1-5) 5
Liquid PH 7.8~8.5
Storage temperature, °C -40~70
Operation humidity(non-condensing), RH 10~90%

Notes:

(1-1) Caution: Wrong input voltage may cause server damaged.
(1-2) Three-phase AC input.
(1-3) The External cooler should be placed outdoors in a well-ventilated environment.
(1-4) If the water conductivity is ≥100 μs/cm, the fluid must be replaced. The water conductivity is less than 20 μs/cm when the system is running at the first time.

(1-5) The maximum distance between mining cabinet and external cooler.

Reviews

There are no reviews yet.

Be the first to review “SPOT ANTRACK AR31”