| Specifications


 

Specification Details For ANTSPACE HD5

Product Overview Value
Model ANTSPACE HD5 
Dimensions (l*w*h), mm 12192*2438*2896

Miner Capacity

308 units –S23 Hyd. & S21 Hyd. & S19 Hyd. Series miner

PUE@25 ˚C ambient temperature

1.021

Container certification CSC
Safety certification NFPA 79:2021
UL 508A:2018 R8.21
CSA C22.2 No. 14-18
ANSI/ISO 12100:2012
IEC 60204 Ed 5.1 2009
Input Voltage and Frequency 400V±5%, 50/60Hz
Detailed Characteristics Value
Shipping weight, T 11
Operating weight, T 18
Main switch of power distribution cabinets, A 1200×4
Rated current, A 700×4
Normal power, kW 1512
Maximum power, kW 1765
Rated current per Miner, A 10
Inlet cable(1-1)

The inlet copper cables can withstand voltage of above 600V, with the following requirements:
L1 single core cable 400kcMil (185mm²)x8
L2 single core cable 400kcMil (185mm²)x8
L3 single core cable 400kcMil (185mm²)x8
N Single-core cable 400kcMil (185mm²)x4
PE single-core cable 400kcMil (185mm²)x4

Connection interface (Dry Cooling tower) DN100(ISO2852 PN16)
Connection interface (Plate heat exchange interface) DN100(GB/T 9122-2010 PN16)
Flow rate 1(1-2), m³/h 67.2
Flow rate 2(1-3), m³/h 73.9
Quantity of ANTSPACE powered by one 3750kVA Transformer 2

 

Specification Details For Dry Cooling Tower

Product Overview Value
Model EC2-DT Dry Cooler(Container Type)
Dimensions (L*W*H)(mm) 12192*2438*2896
Detailed Characteristics Value
Shipping Weight, T 12
Operating Weight, T 14
Heat Dissipation Capacity, kW 1500
Outlet water temperature @30˚C ambient temperature, ˚C 35±1
Container Certification CSC
Safety Certification NFPA 79:2021
UL 508A:2018 R8.21
CSA C22.2 No. 14-18
IEC 60204 Ed 5.1 2009
Input Voltage and Frequency 400V±5%, 50/60Hz
Operationg Power, kW ≤80
Connection interface (Container) DN100(ISO2852 PN16)
Connection Interface (Drain Pipe) DN25(Tapered tube)
Noise @25℃, 15m, dBA 75
Coolant Usage, m³ 2.1

Notes:

(1-1) For aluminum cables, refer to electrical specifications and use copper-aluminum composite terminals that meet standard requirements.

(1-2) Corresponding to 140 miners on one side, the main pump frequency of about 41 Hz.

(1-3) Corresponding to 154 miners on one side, the main pump frequency of about 45 Hz.

Reviews

There are no reviews yet.

Be the first to review “SPOT ANTSPACE HD5”